SAVA Demo data
All sites

Apollo2_New

1,200 kW installed, 12 inverters, commissioned 2023. The site is producing at 95.9% of expectation right now.

Attention requiredData quality 94/100

Site health

Health score out of 100

Current production

742kW

Energy this period

214.6MWh

Expected 223.8 MWh

Estimated loss

8.6MWh

€948

Availability

98.1%

Inverter comparison

An underperforming device stands out immediately against its peers

Inverter comparison for the period

Units: MWh produced

What to notice: Ring3 Inv 1 produced 12.4 MWh while comparable inverters produced around 18.5 MWh over the same period.

Inverter status over time

A quick view of where and when problems occurred

Inverter status over time

One cell per device per day

Device111213141516171819202122232425262728010203
Ring1 Inv 1
Ring1 Inv 2
Ring1 Inv 3
Ring2 Inv 1
Ring2 Inv 2
Ring2 Inv 3
Ring3 Inv 1
Ring3 Inv 2
Ring3 Inv 3
Ring4 Inv 1
Ring4 Inv 2
Ring4 Inv 3
NormalPartial outputFault or stoppedNo data

What to notice: The continuous red row is Ring3 Inv 1. The grey block on Ring1 Inv 2 is missing data, not a fault.

Daily energy

Produced energy and estimated loss per day

Daily energy against expectation

Units: kWh per day

What to notice: Loss is estimated from peer expectation and shown on top of produced energy.

Inverters

Open a device for technical detail

Open incidents at this site

HighActive nowInsulation resistance condition91%High confidence

Persistent insulation resistance condition on Ring3 Inverter 1

Ring3 Inverter 1 has been underperforming since 1 February. The most likely cause is an insulation resistance problem. Estimated production loss is approximately 3.2 MWh.

Location
Apollo2_New · Ring3_Inverter1
Estimated loss
3,204 kWh
Financial impact
€352
Duration
31 days

Next step: Inspect DC cabling and connectors on the affected strings for moisture and damage

MediumActive nowMPPT imbalance64%Moderate confidence

Possible MPPT imbalance on Ring3 Inverter 2

Variation between active MPPT energy measurements is approximately 16.5%. This is an investigation candidate rather than a confirmed fault.

Location
Apollo2_New · Ring3_Inverter2
Estimated loss
486 kWh
Financial impact
€53
Duration
26 days

Next step: Compare string layout and orientation against the design documentation

LowActive nowMPPT imbalance58%Low confidence

Possible MPPT imbalance on Ring2 Inverter 1

Variation between active MPPT energy measurements is approximately 11.4%. Worth inspecting during the next site visit.

Location
Apollo2_New · Ring2_Inverter1
Estimated loss
264 kWh
Financial impact
€29
Duration
19 days

Next step: Add a visual check of this array to the next scheduled site visit

LowNot activeMissing data99%High confidence

Missing measurement intervals on Ring1 Inverter 2

409 five minute intervals are missing for this device on 18 and 19 February. This is a data quality issue and not an equipment fault.

Location
Apollo2_New · Ring1_Inverter2
Estimated loss
0 kWh
Financial impact
€0
Duration
34 h

Next step: Re-export the period from the monitoring platform if the raw data is required

MediumActive nowTemperature anomaly76%Moderate confidence

Elevated internal temperature on Ring4 Inverter 2

Internal temperature runs 12 to 16 degrees above comparable inverters during peak hours, with small derating episodes at midday.

Location
Apollo2_New · Ring4_Inverter2
Estimated loss
138 kWh
Financial impact
€15
Duration
9 days

Next step: Inspect and clean ventilation paths and filters

Data quality

Data problems are kept separate from equipment problems

Missing five minute intervals409 of 61,570 records
Duplicate records18 removed
Invalid or missing timestamps0
Missing device identifiers0
Negative active power36 records clamped to zero
Unrealistic power values0 above device capacity
Devices that stopped reporting1 device, 2 days
Constant values for long periods2 sensors flagged
Requested versus available period1 Feb to 3 Mar, complete