Medium76%Moderate confidenceActive nowTemperature anomalyINC-1080

Elevated internal temperature on Ring4 Inverter 2

Internal temperature runs 12 to 16 degrees above comparable inverters during peak hours, with small derating episodes at midday.

Apollo2_New · Ring4_Inverter2 · Started 22 Feb 2025, 11:20

Estimated energy loss

138kWh

Estimated financial loss

€15

Current loss rate

1.1kW

Duration

9 days

Recommended action

Inspect and clean ventilation paths and filters

Why SOL detected this

  • Peak internal temperature 68.4 °C against a peer median of 53.9 °C.
  • Output drops by 4% to 6% during the hottest hour while peers hold output.
  • The gap grows on clear days.

Most likely cause

Restricted cooling, most likely a blocked air path or a degraded cooling fan.

Other possible causes

  • Blocked ventilation grille or filter
  • Failing cooling fan
  • Direct sun exposure on the enclosure
  • Ambient conditions at the mounting position

Recommended inspection

These steps become the technician checklist

  1. 1Inspect and clean ventilation paths and filters
  2. 2Test the cooling fan operation
  3. 3Check for direct sun exposure and consider shading the enclosure

Actual against expected power

Peer comparison for a representative day

Expected against actual power

Units: kW by time of day

What to notice: The dashed line is what comparable inverters produced at the same time. The shaded area is the actual output.