Missing measurement intervals on Ring1 Inverter 2
409 five minute intervals are missing for this device on 18 and 19 February. This is a data quality issue and not an equipment fault.
Apollo2_New · Ring1_Inverter2 · Started 18 Feb 2025, 00:00
Estimated energy loss
0kWh
Estimated financial loss
€0
Current loss rate
Not active
Duration
34 h
Recommended action
Re-export the period from the monitoring platform if the raw data is required
Why SOL detected this
- Expected records for the period: 576. Records present: 167.
- Energy counters continued to increase across the gap, so the device kept producing.
- Other devices at the site reported normally during the same window.
Most likely cause
Data logger or communication gap during the export period.
Other possible causes
- Logger restart
- Network interruption between the site and the monitoring platform
- Export window did not cover the full period
Recommended inspection
These steps become the technician checklist
- 1Re-export the period from the monitoring platform if the raw data is required
- 2Check logger connectivity for this device
Actual against expected power
Peer comparison for a representative day
Expected against actual power
Units: kW by time of day
What to notice: The dashed line is what comparable inverters produced at the same time. The shaded area is the actual output.